Activities of Karin KADENBACH related to 2013/0442(COD)
Plenary speeches (1)
Limitation of emissions of certain pollutants into the air (debate) DE
Amendments (8)
Amendment 196 #
Proposal for a directive
Article 5 – paragraph 1 a (new)
Article 5 – paragraph 1 a (new)
1a. A new approach toward best available techniques in all policy areas relevant to air quality will be carried out in 1 year after the date of transposition.
Amendment 203 #
Proposal for a directive
Article 5 – paragraph 2 – subparagraph 1
Article 5 – paragraph 2 – subparagraph 1
From 1 January 202518 emissions into air of sulphur dioxide, nitrogen oxides, carbon monoxide and particulate matter from an existing medium combustion plant with a rated thermal input above 5 MW shall not exceed the emission limit values set out in Part 1 of Annex II.
Amendment 211 #
Proposal for a directive
Article 5 – paragraph 2 – subparagraph 2
Article 5 – paragraph 2 – subparagraph 2
From 1 January 20320 emissions into air of sulphur dioxide, nitrogen oxides, carbon monoxide and particulate matter from an existing medium combustion plant with a rated thermal input of 5 MW or less shall not exceed the emission limit values set out in Part 1 of Annex II.
Amendment 453 #
Proposal for a directive
Annex IV – point 1
Annex IV – point 1
1. Periodic measurements of SO2, NOx, CO and particulate matter shall be required at least every three years for medium combustion plants the rated thermal input of which is greater than 1 MW and less than 20 MW, and at least annually for medium combustion plants the rated thermal input of which is equal to or greater than 20 MW but less than 50 MW.
Amendment 459 #
Proposal for a directive
Annex IV – point 3 a (new)
Annex IV – point 3 a (new)
3a. Combustion plants and gas turbines with a rated thermal input above 15 MW shall be equipped with analysers for continuous measurement and recording of carbon monoxide concentrations, particulate matter concentrations, oxygen content and temperature of the flue gas.
Amendment 460 #
Proposal for a directive
Annex IV – point 3 b (new)
Annex IV – point 3 b (new)
3b. Combustion plants and gas turbines with a rated thermal input above 30 MW shall be equipped with analysers for continuous measurement and recording of nitrogen oxides concentrations, sulphur dioxide concentrations, oxygen content and temperature of the flue gas.
Amendment 461 #
Proposal for a directive
Annex IV – point 3 c (new)
Annex IV – point 3 c (new)
3c. Continuous measurements pursuant to points 3a and 3b can be replaced by other adequate tests that ensure compliance with the given emission limit values (e.g. continuous function tests of the flue gas cleaning systems, of the composition of the used fuels or of process parameters).
Amendment 462 #
Proposal for a directive
Annex IV – point 3 d (new)
Annex IV – point 3 d (new)
3d. All equipment mentioned in points (3a) to 3(c) for the continuous measurement shall be installed as from the date of construction of new plants.